INSTRUCTION LEAFLETContains vital information on unit operation and installation.Read and retain carefully. If you are just installing this unit thisl
Other than the cleaning described above, no other customerservicing of this product is required. Repairs, when needed,must be performed by the manufac
contamination build-up for example) the alarm can besilenced by disconnecting the 12 Volt supply. Disconnect thealarm with the red light flashing - as
1. Check room doors for heat orsmoke. Do not open a hot door. Usean alternate escape route. Closedoors behind you as you leave.2. If smoke is heavy, c
Heat Alarms on both sides of closed doors and installingmore than one Smoke / Heat Alarm as recommended in thisleaflet very significantly improves th
FIVE YEAR PRODUCT GUARANTEEEi Electronics guarantees this product (excluding battery)against any defects that are due to faulty material orworkmanship
MODEL (Ei105R4)Supply Voltage: 8.0 to 16.0 VoltsStandby Current: 250 Microamps (max)Alarm Current: 20 to 60 mACable: Multicore low voltage signal cabl
FREQUENT NUISANCE ALARMS OCCUR:(1) Close kitchen / bathroom door when in use.(2) Ensure that the alarm is sited at least 6m away fromsources of fumes.
2READ THIS FIRSTCLEAN YOUR SMOKE ALARM REGULARLY. THISWILL REDUCE THE RISK OF FALSE ALARMS.REMOVE OR COMPLETELY COVER YOUR SMOKEALARM WHEN REDECORATIN
All the Heat Alarms and Smoke Alarms should beinterconnected to ensure the early warning will be heard,particularly by somebody sleeping. A properly d
Single Storey DwellingIf the Home is on one level (a bungalow or mobile home forexample) you should put the first Smoke Alarm in a corridor orhallway
downstairs Smoke Alarm is unlikely to detect the smoke froma fire in a bedroom upstairs (see figure 1).Recommended ProtectionFor recommended protectio
walls etc). Temperature differences might stop smoke orheat from reaching the unit.• Next to or directly above heaters or air conditioning vents,windo
Wall Mounting (Smoke Alarm only)When a ceiling position is not practical (for example on aceiling having exposed beams or joists, or built-in radianth
maximum recommended cable resistance is 20 ohms. Allwiring must comply with local codes. Screw unit to ceilingusing screws provided. Put cover back on
After InstallationTest all units by pressing the test buttons in sequence. TheSmoke/Heat Alarm horn should sound within 10 seconds andthe relay contac